Lab 03: Machine Status Stack Light

 

Application Scenario

Walk through any modern factory and you will see stack lights (tower lights) mounted on top of CNC machines, packaging lines, and robot cells. A supervisor standing across the floor can tell the status of every machine at a glance, without walking over to read a screen.

In this lab you will add a two-color status indicator to the conveyor from Lab 02:

  • G1 (green): conveyor RUNNING.
  • R1 (red): conveyor STOPPED, with control power present.

If both lamps are dark, the control circuit has no power. That is a useful third piece of information for a maintenance technician.

Learning Outcomes

After this lab you will be able to:

  • Use the N.O. and N.C. sides of one contact set to control two loads.
  • Explain why the two lamps can never be ON at the same time.
  • Use indicator lamps to diagnose the state of a control circuit.
  • Describe the difference between machine and utility lamp color conventions.

Required Components

DeviceTypeRole in this lab
PB1 Push button, N.O. START
PB2 Push button, N.C. STOP
CR1 Control relay Conveyor motor contactor (simulated)
G1 Green lamp Conveyor RUNNING
R1 Red lamp Conveyor STOPPED

Background

One contact set, two loads. Contact set CR1B has three pins: common 8, N.O. 6, and N.C. 5. The common is connected to either pin 6 or pin 5, never both:

  • Coil OFF: 8–5 is closed, so R1 is ON.
  • Coil ON: 8–6 is closed, so G1 is ON.

Because the common switches from one side to the other, it is physically impossible for both lamps to be ON at the same time. This is called a changeover (or Form C) contact.

How it looks on the ladder. In the ladder diagram, CR1B appears twice: as an N.O. contact on Rung 3 and as an N.C. contact on Rung 4. On the relay base, both symbols are the same contact set sharing pin 8. Because both rungs start at L1, one wire from L1 to CR1:8 feeds both of them.

Lamp color conventions. Colors do not mean the same thing everywhere:

  • Machine stack lights (NFPA 79 / IEC 60204-1): green = normal operation, amber = warning or abnormal condition, red = emergency or fault. Many plants also use red to mean "stopped".
  • Electric utility switchgear in North America often uses the opposite convention: red = breaker closed (energized, dangerous), green = breaker open (de-energized).

Always check which convention your plant uses before you read a panel.

Ladder Diagram

L1 (+24V) L2 (GND) 1 2 3 4 PB2 (N.C.) 1 2 N2 PB1 (N.O.) 1 2 N3 CR1 2 7 1 3 CR1A (N.O.) seal-in CR1B (N.O.) 8 6 N4 G1 (green) 1 2 CR1B (N.C.) 8 5 N5 R1 (red) 1 2
  • Rungs 1–2: The same three-wire start/stop circuit as Lab 02.
  • Rung 3: CR1B N.O. (8–6) turns G1 ON while the conveyor is running.
  • Rung 4: CR1B N.C. (8–5) turns R1 ON while the conveyor is stopped. The slash through the contact symbol marks it as N.C.

Contact Allocation

RelayPartPinsUsed in
CR1 Coil 2–7 Rung 1
CR1 CR1A N.O. 1–3 Rung 2 (seal-in)
CR1 CR1B N.O. 8–6 Rung 3 (G1)
CR1 CR1B N.C. 8–5 Rung 4 (R1)
CR1 CR1A N.C. 1–4 Not used

Wiring List

Wires 1–9 are the same as Lab 02. Only Wires 10 and 11 are new.

☐Rung#Wire#FromToPurpose
☐ 1 1 L1 PB2:1 +24 V to STOP button
☐ 1 2 PB2:2 PB1:1 STOP to START (N2)
☐ 2 3 PB2:2 CR1:1 STOP to seal-in common (N2)
☐ 1 4 PB1:2 CR1:2 START to relay coil (N3)
☐ 2 5 CR1:3 CR1:2 Seal-in jumper on relay base (N3)
☐ 1 6 CR1:7 L2 Coil return to GND
☐ 3 7 L1 CR1:8 +24 V to CR1B common (feeds rungs 3 and 4)
☐ 3 8 CR1:6 G1:1 CR1B N.O. to green lamp (N4)
☐ 3 9 G1:2 L2 Green lamp return to GND
☐ 4 10 CR1:5 R1:1 CR1B N.C. to red lamp (N5) — new
☐ 4 11 R1:2 L2 Red lamp return to GND — new

Tip: Rung 4 does not need its own wire from L1. Pin 8 is already connected to L1 by Wire 7, and it is the common for both the N.O. side (pin 6) and the N.C. side (pin 5).

Operating Sequence

StepOperator actionCR1 coilCR1B 8–6CR1B 8–5G1R1
1 Power ON, no button pressed OFF Open Closed OFF ON
2 Press and release PB1 (START) ON Closed Open ON OFF
3 Press and release PB2 (STOP) OFF Open Closed OFF ON
4 Control power lost OFF Open Closed OFF OFF
5 Control power restored OFF Open Closed OFF ON

Procedure

  1. Power OFF the trainer (or unplug the power cord).
  2. If your Lab 02 circuit is still wired, verify it against Wires 1–9. Otherwise, wire Wires 1–9 first.
  3. Add Rung 4: Wires 10 and 11.
  4. Check your work against the wiring list, one wire at a time. Mark each wire as checked.
  5. Meter check, power still OFF:

    Reading the meter: once the circuit is wired, the meter can find a path through coils and lamps. A reading of tens to thousands of ohms is normal and counts as high. Only a reading near 0 Ω means a direct connection.

    • CR1:8 to CR1:5 should read near 0 Ω.
    • CR1:8 to CR1:6 should read high (the meter reads through G1 and R1 in series).
    • L1 to CR1:8 should read near 0 Ω (Wire 7).
  6. Ask your lab partner to do a buddy check, then show the instructor.
  7. Power ON and complete the test table below.

Test & Acceptance

#TestExpected result✓
1 Power ON, do nothing R1 ON, G1 OFF ☐
2 Press and release PB1 G1 ON, R1 OFF ☐
3 Start and stop several times while watching both lamps The two lamps are never ON at the same time ☐
4 Press and release PB2 R1 ON, G1 OFF ☐
5 Hold PB2, then press PB1 R1 stays ON; G1 stays OFF ☐
6 Start the conveyor, then switch power OFF Both lamps dark (no control power) ☐
7 Switch power back ON R1 ON, G1 OFF (conveyor does not restart) ☐

Troubleshooting

SymptomLikely causeWhat to check
Lamps are reversed (red while running) Wires 8 and 10 swapped Wire 8 must land on CR1:6; Wire 10 on CR1:5
R1 stays ON all the time R1 bypasses the relay contact Wire 10 must come from CR1:5, not from L1
R1 goes OFF while PB2 is held down R1 is wired to CR1A instead of CR1B CR1A's common is N2 (after STOP). Move Wire 10 to CR1:5
R1 never turns ON Rung 4 open Wire 10 at CR1:5; Wire 11 from R1:2 to L2
G1 and R1 both OFF with power ON No power at CR1B common Wire 7 from L1 to CR1:8

Review Questions

  1. Explain, using the pin numbers of CR1B, why G1 and R1 can never be ON at the same time.
  2. A student connects R1 to CR1:4 instead of CR1:5. At first the circuit seems to work: R1 is ON when the conveyor is stopped. What does R1 do while PB2 is held down? Why? (Hint: trace where CR1A's common gets its power.)
  3. A technician walks up to a machine and sees that both stack lights are dark. What does this tell them? What would they check first?
  4. You transfer from a manufacturing plant to an electric utility substation. A panel lamp is red. Why must you find out which color convention the site uses before you touch anything?

Extension: Lamp Test

Real control panels have a LAMP TEST button that lights every indicator at once, so a burned-out bulb is not mistaken for a "stopped" or "running" signal.

Power OFF. Wire PB3 (N.O.) so that PB3:1 connects to L1, and PB3:2 connects to both G1:1 and R1:1. Power ON and press PB3: both lamps should light. Release PB3: normal status returns.

Think about it: while PB3 is pressed, nodes N4 and N5 are tied together. Why does this cause no problem in our circuit? (Hint: what voltage is on CR1:8?) Industrial panels usually isolate each lamp with a diode or a dedicated lamp-test relay so circuits cannot feed back into each other.

© 2026 Air Supply Information Center (Air Supply BBS)